- 스프링클러 헤드의 응답시간지수 측정
- A Study on Response Time Index for Sprinkler Head
- ㆍ 저자명
- 태순호,이병곤
- ㆍ 간행물명
- 한국산업안전학회지
- ㆍ 권/호정보
- 1990년|5권 3호|pp.51-55 (5 pages)
- ㆍ 발행정보
- 한국안전학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This study describes the engineering approach adopted to investigate sprinkler head during the early stage of a fire when they are subjected to convective heating and low gas velocities. Comparions are made between the parameters derived using basic methods, ie. ramp test, for evaluating sprinkler parameters(time constant, response time index) is illustrated. Evidence is presented that the propotion of heat loss by conduction from a sprinkler element may very typically employed in the rate of rise test. This fact alone may justfy the precautionary need to perform a limited number of rate of rise tests to confirm a sprinklers capacity to function correctly in reasonably unfavourable yet realistic conditions. The work is aimed primarily at meeting the needs of sprinkler industry.