- 부분적인 필터교체에 따른 청정실내부의 유동특성
- Flow Characteristics in a Clean Room after Divisional Filter Exchange
- ㆍ 저자명
- 이재헌,박명식
- ㆍ 간행물명
- 大韓機械學會論文集
- ㆍ 권/호정보
- 1993년|17권 8호|pp.2110-2121 (12 pages)
- ㆍ 발행정보
- 대한기계학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
A numerical investigation has been carried out for the flow characteristics after exchange of some filters from the original layer to the new low pressure loss layer with equal filtering efficiency. The solution domain includes upper plenum, filter layer, clean space, access panels, and lower plenum. The concept of the distributed pressure resistance was applied to describe the momentum loss in filter layer and access panels. The evolution of the flow field is simulated using the low Reynolds number k-.epsilon. over bar turbulent model and SIMPLE algorithm based on the finite volume method. As a result, after the exchange of filter layer the power requirement can be reduced by 8-9 percent. The results also demonstrate that the perpendicularity of the flow near access panels may become worse at new filter layer than origianl filter layer. But the situation can be recovered by adjusting the jopening ratio of access panels.