- 부하반환법에 의한 20KVA 비정질 변압기의 경년열화 연구
- ㆍ 저자명
- 민복기,송재성,정영호,임정재
- ㆍ 간행물명
- 電氣學會論文誌
- ㆍ 권/호정보
- 1994년|43권 2호|pp.278-285 (8 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Aging test was done by loading back method for 20kVA amorphous core transformers manufactured by Hyosung Industries Co. and korea Electric Power Corporation. Iron losses, copper losses and insulation oil temperatures of the transfromers was measured for all the testing period. Expected life of amorphous core transformers on the basis of the degradation of the insulators was 46 years at 100% load, and 2.4 years at 130% load. Average temperature rising of transformer oil of amorphous core transformers was higher than that of silicon steel core transformers. Hence lowering the oil temperature by optimized design is needed for improving the expected life of the amorphous transformers.