- FTA기법에 의한 원전기동전원의 이용율 예측에 관한 연구
- ㆍ 저자명
- 최규식,Che. Gyu-Shik
- ㆍ 간행물명
- 전기학회논문지. The transactions of the Korean Institute of Electrical Engineers. A / A, 전력기술부문
- ㆍ 권/호정보
- 1999년|48권 5호|pp.517-523 (7 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The Start-up transformers or on-site stand-by transformers are installed for the start-up and shut-down of generator and emergency status in unclear power plant. The on-site power supply configuration using these transformers must be detemined by considering configuration requirements, site characteristics, reliability and availability severely because it is remarkably important for safety and benefit of plant. The start-up or stand-by power supply configuration has been determined considering only safety requirements and construction cost up to now in Korea. I study various reliability estimating methods for the prediction of availability, and estimate the unavailability for the start-up power supply system of two 1,000㎿ unclear power plants. I also detemine the reliability and unavailability and unavailavility of equipment, system and configuration using FTA method.