- NTU법을 이용한 대향류형 냉각탑의 성능해석에 관한 연구
- ㆍ 저자명
- 김영수,서무교,이상경
- ㆍ 간행물명
- 空氣 調和·冷凍 工學 論文集
- ㆍ 권/호정보
- 1999년|11권 5호|pp.598-604 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The thermal performance of cooling towers is affected by the temperature of inlet water, wet bulb temperature of entering air add water-air flow rate. In this study, the effects of these variables are simulated using NTU-method and experimentally investigated for the counter-flow cooling towers. The simulation program to evaluate these variables which affect the performance of cooling tower was developed. The maximum errors between the results of simulations and experiments were 3.8% under the standard design conditions and 5.4% under the other conditions. The performance was increased up to 46~50% as the water loading was increased from $6.8m^3$/$hrcdot m^2$ to $15.9m^3$/$hrcdot m^2$. The range was reduced up to 56~42% when the wet bulb temperature of the entering air was increased from $22^{circ}C; to; 29^{circ}C$