- 엔진구동 지열 열펌프의 성능 분석(III) - 대체냉매를 이용한 증기압축식 열펌프의 운전특성 -
- ㆍ 저자명
- 김영복,이승규,김성태,송대빈,강호철
- ㆍ 간행물명
- 한국농업기계학회지
- ㆍ 권/호정보
- 1999년|24권 6호|pp.513-522 (10 pages)
- ㆍ 발행정보
- 한국농업기계학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This study was performed to get the optimal operating conditions of an water-air compact heat pump system using R-134a. The experiments was done for three elvels of the air mass flow rate and the compressor driving speed during air-heating process. The temperature of the air at the condenser inlet and outlet was 17~23$^{circ}C$, 36~44$^{circ}C$, respectively. The average temperature of the refrigerant at the evaporator and condenser was 1$0^{circ}C$, 6$0^{circ}C$, respectively. The temperature of the refrigerant was not depending on the air mass flow rate and the compressor driving speed. The pressure of the refrigerant at the condenser inlet and outlet was ranged of 10~18.5kg/$ extrm{cm}^2$ and that at the evaporator was ranged of 3.1~3.3kg/$ extrm{cm}^2$. The pressure drop at the condenser and evaporator was about 1.5, 1.2 kg/$ extrm{cm}^2$, respectively. The performance of coefficient for air heating was about 3.3~4.0.