- 태양열 이용 냉난방 공조시스템 중 전열교환기의 최적운전조건에 관한 연구
- ㆍ 저자명
- 김광호,최광환,금종수,김보철,김동규,Kim. K.H.,Choi. K.H.,Kum. J.S.,Kim. B.C.,Kim. D.G.
- ㆍ 간행물명
- 태양에너지
- ㆍ 권/호정보
- 1999년|19권 4호|pp.55-62 (8 pages)
- ㆍ 발행정보
- 한국태양에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This study was performed to find out the influence of experimental factors on dehumidification performance and furthermore to suggest an optimal combination of factors of a total heat exchanger in a solar air conditioning system. The experimental apparatus was set up in a climate-controlled chamber where the temperature and humidity was maintained constant. In order to find out the contribution ratio of factors on dehumidification performance, the table of orthogonal arrays $L_8(2^7)$ was used. According to the results, the most influential factor on dehumidification performance was the concentration of LiCl(Lithium Chloride) solution. The next influential factors were the temperature of LiCl solution and the air flow rate. The packed layer height, packed material, and flow rate of LiCl solution had no influence on the dehumidification performance under these experimental conditions. Through the three level experiments of $L_{27}(3^{13})$, it was found that the optimal combination was $A_2B_0G_2$(concentration of solution 30 wt%, temperature of solution $15^{circ}C$, air flow rate $253m^3/h$).