- 공동주택의 냉방시 실내온열환경 평가 연구
- ㆍ 저자명
- 김난행,안병욱
- ㆍ 간행물명
- 한국주거학회 논문집
- ㆍ 권/호정보
- 2003년|14권 3호|pp.1-8 (8 pages)
- ㆍ 발행정보
- 한국주거학회|한국
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
It is not sufficient to control the indoor thermal environment using only one or two parameters by itself as human response for the control of indoor thermal environment. So a proper environmental thermal index is required for the control of indoor thermal environment effectively. In this study, the physical environment was measured and analysed and the skin temperature of the subjects and their response were investigated to evaluate the optimum thermal comfort range for cooling season in an apartment house. As a result, the optimal temperature was 26.1$^{circ}C$ and the temperature ranges which more than 80% responded as satisfactory were 24.1~28.$0^{circ}C$, respectively. As the OT had most significant interrelation with the PMV, it is desirable to use the OT in evaluating the thermal environment during cooling. Also, the comfort range was concluded between OT 25.5~27.3$^{circ}C$ by appointing the PMV of -0.5~0.5 as the optimum comfort condition. In addition, the Human responses were compared with calculated PMV, OT and MRT and the relationships are suggested in order to utilize to control indoor thermal environment.