- 실내 공기정화 시스템에 의한 실내 오염입자의 제거특성에 관한 실험적 연구
- ㆍ 저자명
- 김성찬,이창건,안영철,이재근,강태욱,이감규,구정환
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2003년|15권 9호|pp.733-737 (5 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The purpose of this study is to analyze the particle removal characteristics of a commercial air cleaner based on the electrostatic precipitator. The air cleaner consists of a positive corona precharger to precharge particles and a collector to remove the charged particles. The test for particle removal efficiency is conducted with tobacco smoke particles of 1.27${mu}{ extrm}{m}$ in mass median diameter. The result of one-pass filtration test shows that the filtration efficiency is more than 90% for the particles larger than 2.5 Um, while the efficiency for the particles of 0.5~1.0${mu}{ extrm}{m}$ in case of 4.18 CMM is 70%. For the test room of 5,800${ imes}$3,400${ imes}$2,600㎣, the concentration of tobacco smoke particles decreases up to 30% of initial values within 30 minutes due to natural reduction and up to 90% of initial values within 30 minutes with the air cleaner operation.