- 파울링 형성 가속장치를 이용한 공기조화기용 열교환기의 공기측 파울링 특성에 대한 실험적 연구
- ㆍ 저자명
- 안영철,조재민,이재근,이현욱,안승표,윤덕현,하삼철,강태욱,옥주호
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2003년|15권 10호|pp.802-808 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The air-side particulate fouling of the HVAC heat exchangers degrades the performance of cooling capacity, pressure drop across a heat exchanger, and indoor air quality. The purpose of this study is to investigate the fouling characteristics using accelerated particle loading system. The fouling characteristics are analyzed as functions of a dust concentration, a face velocity and a wet or dry surface condition. The pressure drop increases with increasing test operation and reaches constant asymptotic level. For the saturated condition due to particle loading, the pressure drop across the slitted finned-tube heat exchangers at the face velocity of 1 m/sec increases up to 57% and the cooling capacity decreases about 2%. The cooling capacities are not affected greatly by the presence of the fouling deposits if the thickness of the fouling deposits can not change substantially the flow pattern through the fins.