- 응축기의 설계조건에서 R22, R407C, R410A의 압력강하 예측 및 실험
- ㆍ 저자명
- 김창덕,박일환,이진호
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2004년|16권 1호|pp.42-53 (12 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
An experimental study on the refrigerant-side pressure drop of slit fin-tube heat exchanger has been carried out. A comparison was made between the predictions of previously proposed empirical correlations and experimental data for the pressure drop on design conditions of condenser in micro-fin tube for R22 and its alternatives, R407C (R32/125/134a, 23/25/52 wt.%) and R410A (R32/125, 50/50 wt.%). Experiments were carried out under the conditions of inlet refrigerant temperature of 6$0^{circ}C$ and mass fluxes varying from 150 to 250 kg/$m^2$s for R22, R407C and R410A. The inlet air conditions are dry bulb temperature of 35$^{circ}C$, relative humidity of 40% and air velocity varying from 0.68 to 1.43 m/s. Experiments show that pressure drop for R410A and R407C were 17.8∼20.2% and 5∼6.8% lower than those of R22 respectively for the degree of subcooling of 5$^{circ}C$. For the mass fluxes of 200∼250 kg/$m^2$s, the deviation between the experimental and predicted values for the pressure drop was less than $pm$20% for R22, R407C and R410A.