- FDS를 이용한 실내화재 모사의 문제점 I. 중심형 화재
- A Numerical Study of a Room Fire for Fire Sizes I. Center Fire
- ㆍ 저자명
- 고경찬,박외철,Ko. Kyung-Chan,Park. Woe-Chul
- ㆍ 간행물명
- 산업안전학회지
- ㆍ 권/호정보
- 2004년|19권 1호|pp.18-22 (5 pages)
- ㆍ 발행정보
- 한국안전학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The Fire Dynamics Simulator (FDS) was applied to a center fire in a room, of which dimensions were 1.8m${ imes}$1.38m with an opening of 0.45m${ imes}$1.2m doorway, to evaluate the numerical method. The time-variation of temperature at a top point of thedoorway centerline and distributions of evaluate the numerical method. The time-variation of temperature at a top point of the doorway centerline and distributions of average temperature along the doorway centerline and corner stack were compared with measurements for three different fire sizes, 7.65, 21.25 and 51.71kW. The results showed FDS predicted a very rapid fire growth compared with the experiment for all the three fire sizes, that is an importand shortcoming of FDS in compartment fire simulations. The average temperature distributions, and heights of hot gas layers and neutral planes in steady state were in reasonable agreement with the measurements.