- LCC 분석에 의한 하천수 미활용에너지 이용시스템의 경제성 평가
- ㆍ 저자명
- 박일환,윤형기,장기창,박준택,박성룡,Park. Il-Hwan,Yoon. Hyung-Kee,Chang. Ki-Chang,Park. Jun-Taek,Park. Seong-Ryong
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 6호|pp.596-604 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper presents the work on evaluating the LCC (Life-Cycle Cost) of a heat pump system as unutilized energy system. The river water as an unutilized energy source was used for the heat source of heat pump system. LCC analysis is a concrete method for evaluating the economical efficiency of energy facilities of building. The present case study shows an example of adequate use of the LCC analysis on a heat pump system and conventional gas boiler and refrigerator for building heat supply. A life cycle of 20 years was used to calculated net present value of energy cost. Over a 20 year life cycle, the energy cost could be reduced by 612 million won if a heat pump system were used instead of a conventional boiler and an absorption refrigerator.