- 폴리프로필렌 모세유관 냉방시스템의 적용에 관한 실험적 연구
- ㆍ 저자명
- 이영주,김오봉,김광우,여명석,Lee. Young-Ju,Jin. Wu-feng,Yeo. Myoung-Souk,Kim. Kwang-Woo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 9호|pp.873-881 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, we made RFC, RCC and NCC according to the method by which polypropylene capillary tube was adopted, and evaluated cooling performance of each system through model experiments. We also investigated an applicability of the combined use of radiant cooling and dehumidification system. The results are as follows: In case of normal cooling load, RFC and RCC maintained set temperature without a condensation. But, in case of peak cooling load, RFC and RCC resulted in the lack of cooling performance and caused a condensation at the radiation surface. Consequently, the only use of polypropylene capillary tube is considered not to be enough for cooling in real application. Using the combination of a dehumidification and radiant cooling system maintained the set temperature without a condensation. NCC kept the set temperature at anytime without a condensation. It is more economic than packaged air-conditioner system due to the cooling effect of the floor surface.