- 저온용 R502 대체냉매의 성능 평가
- ㆍ 저자명
- 하종철,황지환,백인철,정동수,Ha. Jong-Chul,Hwang. Ji-Hwan,Baek. In-Chul,Jung. Dongsoo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 10호|pp.883-890 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, 2 pure hydrocarbon refrigerants of R1270 (Propylene) and R290 (Propane) and 3 binary mixtures composed of R1270, R29O and R152a were tested in a refrigerating bench tester with a scroll compressor in an attempt to substitute R502 used in most of the low temperature applications. The test bench provided 3sim3.5$ kW capacity and water and water/glycol mixture were employed as the secondary heat transfer fluids. All tests were conducted under the same external conditions resulting in the average saturation temperatures of -28 and $45^{circ}C$ in the evaporator and condenser, respectively. Test results showed that all refrigerants tested had $9.6sim18.7\%$ higher capacity and $17.1sim27.3\%$ higher COP than R502. The compressor discharge temperature of R1270 was similar to that of R502 while those of all other refrigerants were $23.7sim27.9\%$ lower than that of R502. For all alternative refrigerants, the amount of charge was reduced up to $60\%$ as compared to R502. Overall, these alternative refrigerants offer better system performance and reliability than R502 and can be used as long term substitutes for R502 due to their excellent environmental properties.