- 부분방전 해석 방법으로 PSA(Pulse Sequence Analysis)의 현장 적용성에 대한 고찰
- ㆍ 저자명
- 김정태,이호근,Kim. Jeong-Tae,Lee. Ho-Keun
- ㆍ 간행물명
- 전기전자재료학회논문지
- ㆍ 권/호정보
- 2005년|18권 5호|pp.484-489 (6 pages)
- ㆍ 발행정보
- 한국전기전자재료학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Because of its effectiveness for the PD(Partial Discharge) pattern recognition, PSA(Pulse Sequence Analysis) has been considered as a new analytic method instead of conventional PRPDA(Phase Resolved Partial Discharge Analysis). However, it is generally thought that PSA has some possibility to misjudge patterns in case of data-missing resulting from poor sensitivity because it analyses the correlation between sequential pulses, which leads to hesitate to apply it to on-site. Therefore, in this paper, the problems of PSA such as data-missing and noise-adding cases were investigated. for the purpose, PD data obtained from various defects including noise-adding data were used and analyzed. As a result, it was shown that both cases could cause fatal errors in recognizing PD patterns. In case of the data missing, the error was dependant on the kinds of defect and the degree of degradation Also, it could be noticed that the error due to adding noises was larger than that due to some data missing.