- HFC134a 만액식 증발전열관 외부형상 변화에 따른 열전달 특성실험
- ㆍ 저자명
- 양승우,이영수,정진희,강용태,Yang. Seung-Woo,Lee. Young-Su,Jeong. Jin-Hee,Kang. Yong-Tae
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2006년|18권 12호|pp.971-976 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The objectives of this paper are to study the characteristics of pool boiling heat transfer for enhanced tubes used in the evaporator of turbo chiller and to provide a guideline for optimum design of an evaporator using HFC134a. Three different enhanced tubes are tested at 4 different saturation temperatures. The wall super heated temperature difference ranges from $0.5^{circ}C;to;3.5^{circ}C$. The refrigerant, HFC134a evaporates on the outside of the tube while the chilled water flows inside the tube. This study provides experimental heat transfer coefficients for evaporation on the enhanced tubes. It is found that the turbo-II tube provides the highest heat transfer coefficient.