- 건식이중바닥온돌시스템 개발을 위한 실험적 연구
- ㆍ 저자명
- 김난행,손장열,Kim. Nan-Haeng,Sohn. Jang-Yeul
- ㆍ 간행물명
- 한국주거학회 논문집
- ㆍ 권/호정보
- 2006년|17권 3호|pp.1-7 (7 pages)
- ㆍ 발행정보
- 한국주거학회|한국
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The aim of the research was to evaluate the characteristics of thermal environment and thermal comfort in the Dry Double floors Hydronic Ondol System. Physical indoor thermal environments (the floor surface temperature, the vertical temperature, etc.) and skin temperature have especially been measured. Physical features conditions, sensation, thermal comfort, humidity sensation, comfort of body were investigated for the survey. As a result, (1) During the operation of the boiler (12 hour), the average indoor temperature is appeared to be $21.6^{circ}C$. The floor surface temperature showed peak value of $31.4{sim}40.6^{circ}C$ after 8hours 30minutes after the start-point of the heating. The vertical difference of temperature was turned out to be not uniform. (2) While the skin temperature showed a narrow distribution of temperature in the Dry Double floors Hydronic Ondol system. (3) The response to thermal comfort which people felt was satisfactory, and most of them felt dry during the test.