- 흡수식 냉동기에서 흡수액이 증발기로 혼입시 냉각용량과 성능계수에 미치는 영향
- ㆍ 저자명
- 박찬우,Park. Chan-Woo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2006년|18권 9호|pp.753-760 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The purpose of the present work is to investigate the influence of the refrigerant adulteration by LiBr solution on the cooling capacity and COP for three different types of abso게tion chillers: a single-effect type, a series-flow double-effect type and a parallel-flow with double-effect type. A simulation program has been prepared for the cyclic analysis of absorption chillers. With some assumptions, the calculations have been performed by solving the mass balance equation, energy balance equation and the state equation simultaneously. The range of the LiBr concentration of refrigerant was 0% to 20% in the present study. For the single-effect absorption chiller, the maximum decrease in the cooling capacity was 10% at the 20% of LiBr concentration. For the double-effect chiller, the capacity was decreased by 11.1% for the parallel-flow type and the series-flow type. Also, the COP was reduced by 3.0% in single-effect, 2.8% in series-flow type (SR=0.4) and 2.3% in parallel-flow type.