- 자원회수시설용 폐기물 벙커의 환기설비설계 개선에 관한 연구
- ㆍ 저자명
- 이태구,문정환,허진혁,이재헌,Lee. Tae-Gu,Moon. Jung-Hwan,Hur. Jin-Huek,Lee. Jae-Heon
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2007년|19권 1호|pp.51-59 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The waste bunker usually consists of waste entrance zone and waste pit. In this paper, the distributions of air flow, $NH_3$ concentration and $H_2S$ concentration in a waste bunker were investigated to prevent an odor generated in a waste pit from dispersing to the waste entrance zone by numerical method. Four cases were considered such that 1) the waste incinerators is operated, 2) the waste incinerators is stopped, 3) the waste incinerator is operated and the direction of a supply diffuser is $45^{circ}$ upward, 4) the waste incinerator is stopped and the direction of a supply diffuser is $45^{circ}$ upward. In case of 1), the fresh air from the waste entrance zone is exhausted smoothly to the main exhaust grill of the waste pit. It means that an odor dispersion to the waste entrance zone will not occur. However in case of 2), the induction of fresh air is so small and the supply air with an odor in waste pit can flow to the waste entrance zone. Therefore, an odor will be dispersed to the waste entrance zone. This paper shows the solution that the supply diffuser with the direction of $45^{circ}$ upward is chosen. As a result in case of 3) and 4), an odor dispersion to the waste entrance zone does not occurred and on odor is exhausted smoothly to the auxiliary exhaust grill.