- 공조기가 설치된 고분 내에서의 열 및 음 환경 평가
- ㆍ 저자명
- 박진양,전희호,전용두,이금배,Park. Jin-Yang,Jun. Hee-Ho,Jun. Yong-Du,Lee. Kum-Bae
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2007년|19권 3호|pp.228-234 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Opening an ancient tomb interior can deal fair damage for preservation in long period because of high moisture. In this study, a duct-type HVAC system was installed to preserve an ancient tomb and temperature and humidity was measured to analyze heat environment. Armhole was measured to search whether an ancient tomb receives effects of vibration caused by a duct-type HVAC system. According to the measured data, temperature in an ancient tomb is kept adaptively in conservation regardless of a duct-type HVAC system installation when it rains in summer. The other side, humidity is kept adaptively in conservation when installed duct-type HVAC system. But when it is in natural state, a lot of humidity by dew condensation phenomena. So it needs a duct-type system for an ancient tomb conservation. In the case of vibration, measurement value of 3 satisfy control but Germanic DIN 4150 does not satisfy. Therefore, equip must be such that it can prevent vibration for safety.