- 박스형 이중외피와 커튼월의 냉방기 열적성능에 관한 비교실험 연구
- ㆍ 저자명
- 박창영,이건호,윤용상,최창호,Park. Chang-Young,Lee. Keon-Ho,Yoon. Yong-Sang,Choi. Chang-Ho
- ㆍ 간행물명
- 한국태양에너지학회 논문집
- ㆍ 권/호정보
- 2007년|27권 2호|pp.111-119 (9 pages)
- ㆍ 발행정보
- 한국태양에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The annual mean temperature of South Korea has risen by $1.3^{circ}C$ for last 100 years by urbanization and industrialization. Especially, the frequency of unusual hot weather in summer increases for a long time and the frequency of unusual cold weather in winter clearly decreases. In recently, The considerable portion of curtain wall system is appled to building skin in domestic. As related to this, the Korea Institute of Construction Technology devised the box typed double skin facade(It is occasionally called as FDFS : Functional Double Facade System) as an alternative that reflects the distinctive local climate and saves cooling energy. Two mock-ups($49m^*4.9m$) applied to single skin(curtain wall) and double skin each were monitored under the outdoor condition. Therefore, the characteristics of natural ventilation and cooling energy consumption of each window had been analyzed in real time. The results of this study are summarized as follow, Analysis of the experiment on an air conditioner: the indoor temperature of the chamber with FDFS is lower than that of the chamber with single skin facades by $3{sim}6$ degrees(C). A temperature variation of about $1{sim}2$ degrees between the 0.2m and 1.7m height of the mock-up occurs in FDFS, while that of about maximum 7 degrees occurs in single skin facade at noon with abundant intensity of solar accident. Also, 67 percent of energy consumption for air conditioning has been saved.