- 제트 팬 설치 위치에 따른 직선터널 내의 제연해석
- ㆍ 저자명
- 변주석,임효재,강신형,이진호,Byun. Ju-Suk,Lim. Hyo-Jae,Kang. Shin-Hyung,Lee. Jin-Ho
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2007년|19권 9호|pp.662-668 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, jet fans are installed with 4 cases in the straight long tunnel; inlet-side setup, middle-side setup, outlet-side setup, and dispersion setup. A bus is selected as fired car, of which fire size is 20MW. And fired car locates at 100m, 700m, 1500m position from tunnel inlet, respectively. FLUENT, commercial finite-volume code, is used to analyze the performance. The velocity profile, $CO_2$ concentration, temperature distribution are examined for analysis. Performance of smoke control is compared by the backlayering length. Consequently, inlet-side setup of jet fans is a little more efficient than other cases considering the fire occurrence frequency in tunnel.