- 세관내 R-22와 R-410A의 응축 압력강하
- ㆍ 저자명
- 손창효,Son. Chang-Hyo
- ㆍ 간행물명
- 한국수소 및 신에너지학회 논문집
- ㆍ 권/호정보
- 2008년|19권 2호|pp.156-162 (7 pages)
- ㆍ 발행정보
- 한국수소및신에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The condensation pressure drop for R-22 and R-410A flowing in a small diameter tube was investigated. The test section is a counterflow heat exchanger with refrigerant flowing in the inner tube and coolant flowing in the annulus. The test section consists of 1220 mm length with horizontal copper tube of 3.38 mm outer diameter and 1.77 mm inner diameter. The refrigerant mass fluxes ranged from 450 to $1050;kg/m^2{cdot}s$ and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main experimental results were summarized as follows : In the case of two-phase flow, the pressure drop increases with increasing mass flux and decreasing quality. The pressure drop of R-22 is slightly higher than that of R-410A for the same mass flux. Most of correlations proposed in the large diameter tube showed enormous deviations with experimental data.