- 내경 4.57과 7.75 mm인 수평관내 이산화탄소의 증발 압력강하
- ㆍ 저자명
- 손창효,Son. Chang-Hyo
- ㆍ 간행물명
- 한국자동차공학회논문집
- ㆍ 권/호정보
- 2008년|16권 3호|pp.30-37 (8 pages)
- ㆍ 발행정보
- 한국자동차공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The evaporation pressure drop of $CO_2$ (R-744) in horizontal tubes was investigated experimentally. The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator (test section). The test section consists of a smooth, horizontal stainless steel tube of 7.75 and 4.57 mm inner diameter. The experiments were conducted at saturation temperature of $-5^{circ}C;to;5^{circ}C$, and heat flux of 10 to $40kW/m^2$. The test results showed the evaporation pressure drop of $CO_2$ are highly dependent on the vapor quality, heat flux and saturation temperature. The pressure drop measured during the evaporation process of $CO_2$ increases with increased mass flux, and decreases as the saturation temperature increased. The evaporation pressure drop of $CO_2$ is very lower than that of R-22. In comparison with test results and existing correlations, the best fit of the present experimental data is obtained with the correlation of Choi et al. But existing correlations failed to predict the evaporation pressure drop of $CO_2$. Therefore, it is necessary to develop reliable and accurate predictions determining the evaporation pressure drop of $CO_2$ in a horizontal tube.