- 혼합냉매 R-407C의 증발 열전달과 압력강하
- ㆍ 저자명
- 노건상,오후규,손창효,Roh. Geon-Sang,Oh. Hoo-Kyu,Son. Chang-Hyo
- ㆍ 간행물명
- 한국마린엔지니어링학회지
- ㆍ 권/호정보
- 2008년|32권 4호|pp.542-549 (8 pages)
- ㆍ 발행정보
- 한국마린엔지니어링학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The evaporation heat transfer coefficient and pressure drop of R-22 and R-407C in a horizontal copper tube were investigated experimentally. The main components of the refrigerant loop are a receiver, a compressor, a mass flow meter, a condenser and a double pipe type evaporator (test section). The test section consists of a smooth copper tube of 6.4 mm inner diameter. The refrigerant mass fluxes were varied from 100 to $300;kg/m^2s$ and the saturation temperature of evaporator were $5^{circ}C$. The evaporation heat transfer coefficients of R-22 and R-407C increase with the increase of mass flux and vapor quality. The evaporation heat transfer coefficients of R-22 is about $5.68{ imes}46.6%$ higher than that of R-407C. The evaporation pressure drop of R-22 and R-407C increase with the increase of mass flux. The pressure drop of R-22 is similar to that of R-407C. In comparison with test results and existing correlations, correlations failed to predict the evaporation heat transfer coefficient of R-22 and R-407C. therefore, it is necessary to develope reliable and accurate predictions determining the evaporation heat transfer coefficient of R-22 and R-407C in a horizontal tube.