- 지열히트펌프를 이용한 습식.건식 바닥난방 성능평가 연구
- ㆍ 저자명
- 이병두,이세진,이대우,오성해,남우동,Lee. Byoung-Doo,Lee. Se-Jin,Lee. Dae-Woo,Oh. Sung-Hae,Nam. Woo-Dong
- ㆍ 간행물명
- 신재생에너지
- ㆍ 권/호정보
- 2009년|5권 4호|pp.60-65 (6 pages)
- ㆍ 발행정보
- 한국신재생에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The present study was conducted for a comparative evaluation of wet and dry floor heating systems using geothermal heat pump. We circulated hot water from geothermal heat pump which is $10{sim}15^{circ}C$ lower than that from boiler. In order to access indoor temperature ($25^{circ}C$) it took 74 minutes for dry type and 247 minutes for wet type. Average floor temperature was $23.9^{circ}C$ for wet type and $32.7^{circ}C$ for dry type. Energy saving rate gradually increased by 66% after 138 minutes. As a result, in case of floor heating system using low temperature circulation water, dry type was more practicable for stable floor heating than wet type in terms of floor temperature and access time to indoor set temperature.