- 다른 굵기의 6/10[kV]급 CV 케이블 직선접속부 안전성 평가
- ㆍ 저자명
- 정종욱,김선구,정진수,Jung. Jong-Wook,Kim. Sun-Gu,Jung. Jin-Soo
- ㆍ 간행물명
- 照明·電氣設備學會論文誌
- ㆍ 권/호정보
- 2010년|24권 10호|pp.78-84 (7 pages)
- ㆍ 발행정보
- 한국조명전기설비학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes the safety assessment of power cable splices connecting different sized 6/10[kV] class power cables. To assess the safety, AC withstand voltage tests, partial discharge tests and impulse tests were carried out to the cable splice specimens and thermal rise due to overload and cross section of joint were examined as well. As a result, a breakdown due to the $4.5[U_0](27[kV_{ac}])$ application could not found for 5 minutes. Under $1.73[U_0](10.4[kV_{ac}])$ application, partial discharges of 4~8[pC] were detected. In impulse tests, all the specimens withstood to the standard waveforms of $75[kV_{peak}](1.2{ imes}50[{mu}s])$ without any breakdowns. In addition, the temperature on the splice rose by $3[^{circ}C]$ when the 200[A] flew through the splice for 20minutes, however the thermal rise of $3[^{circ}C]$ was considered due to the atmospheric temperature. After all the electrical tests, the cross section of the splice was visually examined. The conditions of the conductors of both $185[mm^2]$ and $240[mm^2]$ were good.