- 착상과 제상이 냉동장치의 운전특성에 미치는 영향
- ㆍ 저자명
- 김재돌,Kim. J.D.
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2010년|14권 4호|pp.5-10 (6 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This study was investigated the effect on operating characteristics of apparatus according to frosting and defrosting to develop of new defrosting equipment. The results showed as following. Frost was almost removed using the defrosting equipment with roll brush type that defrosting is possible under operating condition. Also, the temperature of compressor inlet, evaporator inlet and outlet showed higher value because of heat transfer resistance of cooling pipe frost comparing with defrosting condition. And the compressor work showed 10% lower and COP was presented 24% higher values than defrosting condition. Therefore, defrosting for cooling coil of refrigeration and low temperature storage was effected on operation and performance characteristics of equipment. This highly effects on real refrigeration apparatus which is operated in year-around.