- 중앙 냉방시스템에 대한 외기보상제어의 절약 성능에 관한 실험적 연구
- ㆍ 저자명
- 김동철,송재엽,안병천,Kim. Dong-Cheol,Song. Jae-Yeob,Ahn. Byung-Cheon
- ㆍ 간행물명
- 한국지열에너지학회논문집
- ㆍ 권/호정보
- 2011년|7권 2호|pp.30-36 (7 pages)
- ㆍ 발행정보
- 한국지열에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, energy saving performance of outdoor temperature reset control strategy for central cooling system is researched by experiments. Outdoor temperature reset control is the control method to change indoor air set temperature according to outdoor air temperature change. The range of indoor air set temperature is represented by the comfort temperature range of indoor air temperature offered from ASHRAE and indoor air set temperature is programmed between $22^{circ}C$ and $27^{circ}C$ by outdoor air temperature $20^{circ}C{sim}32^{circ}C$ in summer. As a result of applying outdoor temperature reset control to central cooling system, the suggested control method shows better performances of energy savings than the conventional method which indoor temperature maintains constantly.