Analysis of Insulation Quality in Large Generator Stator Windings
[STEP1]서지반출 형식 선택
파일형식
@
서지도구
SNS
기타
[STEP2]서지반출 정보 선택
  • 제목
  • URL
돌아가기
확인
취소
  • Analysis of Insulation Quality in Large Generator Stator Windings
  • Analysis of Insulation Quality in Large Generator Stator Windings
저자명
Kim. Hee-Dong,Kong. Tae-Sik,Ju. Young-Ho,Kim. Byong-Han
간행물명
Journal of electrical engineering & technology
권/호정보
2011년|6권 3호|pp.384-390 (7 pages)
발행정보
대한전기학회
파일정보
정기간행물|ENG|
PDF텍스트
주제분야
기타
이 논문은 한국과학기술정보연구원과 논문 연계를 통해 무료로 제공되는 원문입니다.
서지반출

기타언어초록

To evaluate the condition of stator winding insulation in generators that have been operated for a long period of time, diagnostic tests were performed on the stator bars of a 500 MW, 22 kV generator under accelerated thermal and electrical aging procedures. The tests included measurements of AC current (${Delta}I$), dissipation factor ($tan{delta}$), partial discharge (PD) magnitude, and capacitance (C). In addition, the AC current test was performed on the stator winding of a 350 MW, 24 kV generator under operation to confirm insulation deterioration. The values of ${Delta}I$, ${Delta}tan{delta}$, and PD magnitude in one stator bar indicated serious insulation deterioration. In another stator bar, the ${Delta}I$ measurements showed that the insulation was in good condition, whereas the values of ${Delta}tan{delta}$ and PD magnitude indicated an incipient stage of insulation deterioration. Measurements of ${Delta}I$ and PD magnitude in all three phases (A, B, C) of the remaining generator stator windings showed that they were in good condition, although the ${Delta}tan{delta}$ measurements suggested that the condition of the insulation should be monitored carefully. Overall analysis of the results suggested that the generator stator windings were in good condition. The patterns of PD magnitude in all three phases (A, B, C) were attributed to internal discharge.