- 이산화탄소 냉매를 이용한 냉동탑차용 핀-관 증발기의 서리성장에 따른 열교환기 성능에 관한 해석적 연구
- ㆍ 저자명
- 명치욱,조홍현,Myung. Chi-Wook,Cho. Hong-Hyun
- ㆍ 간행물명
- 한국지열에너지학회논문집
- ㆍ 권/호정보
- 2012년|8권 2호|pp.48-54 (7 pages)
- ㆍ 발행정보
- 한국지열에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
To analyze the cooling performance of fin-tube evaporator in the refrigerator truck using R744 according to frost growth, the analytical model of evaporator was developed under frost and non-frost conditions. The performance of fin-tube evaporator was investigated with frost thickness and indoor temperature. Besides, the performance of evaporator under frost condition was compared to that under non-frost condition. As a result, area of air passage and system performance were decreased as the frost thickness increased. The cooling capacity was reduced by 10%, 20%, 30% when the frost thickness was 0.7 mm, 1.1 mm, and 1.6 mm respectively. At these conditions, the block ratio was 31%, 48%, and 71%. In addition, the outlet quality of refrigerant was not over 1 when the frost thickness was 1.6 mm in spite of high indoor air temperature.