- 대향류와 평행류형 판형 증발기에서 운전방식에 따른 성능특성 분석
- ㆍ 저자명
- 배경진,차동안,권오경,Bae. Kyung-Jin,Cha. Dong-An,Kwon. Oh-Kyung
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2013년|17권 3호|pp.50-56 (7 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The analysis of performance characteristics was carried out in the plate type evaporator with counter and parallel flow. To investigate performance of evaporator with water inlet temperature and refrigerant mass flow rate were changed. As a result, when the inlet temperature of water is $8^{circ}C$, capacity of parallel flow evaporator higher than counter flow is 0.35%. But as the inlet temperature of water rises from $8^{circ}C$ to $16^{circ}C$, capacity of counter flow type evaporator higher than parallel flow type is 0.12%, 0.27%, 1.1%, 1.6%, respectively. The findings showed that counter flow type evaporator has a larger capacity than those that were parallel flow type evaporator. As the refrigerant mass flow rate rises, capacity and pressure drop increases in the counter and parallel flow type evaporator.