- 3상 비엔나 정류기 입력 전압 센서리스 제어
- ㆍ 저자명
- 이상리,김학원,조관열,황순상,윤병철,Lee. Sang-Ri,Kim. Hag-Wone,Cho. Kwan-Yuhl,Hwang. Soon-Sang,Yoon. Byung-Chul
- ㆍ 간행물명
- 전력전자학회 논문지
- ㆍ 권/호정보
- 2014년|19권 1호|pp.71-79 (9 pages)
- ㆍ 발행정보
- 전력전자학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this paper, a new grid voltage estimation algorithm without voltage sensors is proposed for the three-phase vienna rectifier. Generally, input voltage sensor circuits increase size and cost of the PWM rectifier In order to reduce the cost and size and in order to increase reliability from the electrical noise, grid voltage estimation scheme without input voltage sensor is highly required. In this paper, the grid voltage estimation algorithm is proposed by a simple MRAS(Model Reference Adaptive System) observer without input voltage sensors. The validity of the proposed method is proven by simulation and experiment on the three-phase vienna rectifier system.