- 발전소용 4.16 kV급 차단기에서 감전사고 사례 분석
- ㆍ 저자명
- 박남규,송재용,김진표,고재모,Park. Nam-Kyu,Song. Jae-Yong,Kim. Jin-Pyo,Goh. Jae-Mo
- ㆍ 간행물명
- 한국안전학회지
- ㆍ 권/호정보
- 2014년|29권 4호|pp.54-60 (7 pages)
- ㆍ 발행정보
- 한국안전학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes electric shock accidents on a 4.16 kV class circuit breaker for power plant. Electric shock accidents mostly involve damage of human life, in comparison with electrical fire, rate of human death tend to be higher in electric shock accidents. Specially, in a high voltage facilities rate of human death comprised about 43.7% by electric shock accidents. If electric shock accidents happen in a 4.16 kV class circuit breaker for power plant, then the power plant discontinue power production. Electric shock accidents in a power plant have a great ripple effect such as an electric power shortage. In this paper, we analyzed electric shock accidents on a 4.16 kV class circuit breaker for power plant. From the analysis results, we confirmed a cause of electric shock accidents on a 4.16 kV class circuit breaker, it happened by defect of interlock equipment or occurrence of breakdown between first feeder contactor and shielding plate. In order to reduce electric shock accidents on a 4.16 kV class circuit breaker, the power plant should consider improvement of interlock equipment and insulation of feeder contactor in circuit breaker.