- 건조기용 타원관 대구경 핀-관 열교환기의 성능특성
- ㆍ 저자명
- 배경진,차동안,권오경,Bae. Kyung-Jin,Cha. Dong-An,Kwon. Oh-Kyung
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2014년|18권 5호|pp.22-27 (6 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The objectives of this paper are to obtain an empirical equations regarding the correlations between heat transfer and pressure drop of oval fin-tube heat exchanger having large diameter using wilson plot method. It was difficult to find any recommendable heat transfer and friction factor correlation available for our large diameter experimental cases. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. The resulting empirical correlations for the Nui and f-factor are given as $Nu_i=0.0146Re^{0.809}Pr^{0.3}$ and $f=4.366Re^{-0.64}$, respectively. The empirical correlations of the Nui and f-factors were developed for the large diameter oval finned-tube heat exchanger as a function of the Reynolds number. As the EG(Ethylene glycol) and air flow rate increases, the heat transfer rate and pressure drop is increased largely.