- 대체냉매 R-407C의 모세관 선정에 관한 연구
- ㆍ 저자명
- 김용환,김창년,박영무
- ㆍ 간행물명
- 空氣 調和·冷凍 工學 論文集
- ㆍ 권/호정보
- 1998년|10권 1호|pp.56-65 (10 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this paper, experimental investigation of capillary tube performance for R-407C is performed. The experimental setup is made of real vapor-compression refrigerating system. In this study, mass flow rate is measured for capillary tubes of various diameter and length as inlet pressure and degree of subcooling are changed. These data are compared with the results of a numerical model. The mass flow rates of the numerical model are less than by 14% compared with the measured mass flow rates. It is found that mass flow rate and length for R-407c are less than those of R-22 under the same condition. Also based on this experimental study and the numerical model, a set of capillary tube selection charts for R-407C is constructed.