- 정풍량방식 덕트에서 이중압력측정방법을 이용한 취출구 풍량조정
- ㆍ 저자명
- 이대우,박명식,박영우
- ㆍ 간행물명
- 空氣 調和·冷凍 工學 論文集
- ㆍ 권/호정보
- 1998년|10권 1호|pp.66-78 (13 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Adequate ventilation with the proper amount of air to the right place is important factor to achieve a good Indoor air climate. Thus it is of prime importance that the ventilation system is working properly. This requires reliable pressure loss calculation to balance the air flow through duct systems. So a computer program for balancing CAV duct system is developed In this study. The results of CAV duct system is compared with the "Balans" code developed by Larsen from Norway. To obtain the pressure drop characteristics of damper at duct terminal, some experiments are performed using DPM(Dual Pressure Measurement) system. To adjust the resistance of damper, present study suggests that some special diffusers should be designed and damper producers should give the data of air flow vs. pressure drop to the customs when they manufacture the damper. One of the results concludes that the working time can be reduced from several minutes to several seconds per damper in the present experimental site, if the DPM system and the air volume adjusting process are used.