- 탄화수소계 냉매 R-290을 사용하는 냉동.공조 장치의 사이클 특성에 관한 연구
- ㆍ 저자명
- 박기원
- ㆍ 간행물명
- 韓國舶用機關學會誌
- ㆍ 권/호정보
- 1999년|23권 4호|pp.447-452 (6 pages)
- ㆍ 발행정보
- 한국마린엔지니어링학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes the cycle performance of heat-pump system using R-22 and R-290. Experi-ments were performed in the smooth tube with inside diameter of 10.07mm and outside diameter of 12.07 mm and grooved inner tube having 75 fins with a height of 0.25mm Condensing temper-atures were held constantly between 318K and 328 K while evaporating temperatures were var-ied from 257 K to 288 K mass velocities from 51 to $280 kg/m^2s.$ From the experiments it was known that the evaporating temperature and condensing tempera-ture had moer affected by the compressor shaft power than the tube geometries. Cooling capacity of the R-22 and R-290 had similar values in the smooth and grooved inner tubes. The coefficient of per-formance(COP) was calculated using the compressor shaft power volumetric refrigeration capacity compression ratio and cooling capacity. The COP of the R-290 had slightly higher values than that of R-22 The major parameters affecting the heat pump cycle performance wee the refrigerant proper-ties and operating conditions rather than the geometric shapes of the heat exchanger