- 중규모 태양광발전시스템 장기 실증운전 평가
- ㆍ 저자명
- 김의환,안교상,임희천,Kim. Eui-Hwan,Ahn. Kyo-Sang,Lim. Hee-Chun
- ㆍ 간행물명
- 한국태양에너지학회 논문집
- ㆍ 권/호정보
- 2009년|29권 5호|pp.14-19 (6 pages)
- ㆍ 발행정보
- 한국태양에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The 50 kWp grid connected photovoltaic system which was installed at KEPRI site in 1999 has been operated more than 10 years. In order to acquire long term operation characteristics of medium size photovoltaic system, the operation test data related on power generation electricity and capacity factor of 50 kWp system, which have been collected since 1999, were analysed. From the analysing results, 57.7 MWh in annual power generation electricity of 50 kWp photovoltaic system in 1999 has been decreased 49.1 MWh in 2005 and reached 41.9 MWh in 2008. In addition to, the capacity factor of 50 kWp photovoltaic system also showed 13.2 % in 1999, 11.2% in 2005 and finally reached 9.6% in 2008. The operation test data showed a trend of decreasing of generation electricity and capacity factor during the 10 years operation time and we guessed that was caused by solar cell performance degradation and decreasing of PCS system efficiency.