- 냉복도 밀폐시스템을 적용한 서버실의 실내온도조건
- ㆍ 저자명
- 정용호,장현재,서장후,Jung. Yong-Ho,Chang. Hyun-Jae,Seo. Jang-Hoo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2013년|25권 2호|pp.79-84 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, a cold aisle containment system was proposed among various strategies to reduce the energy waste by recirculation air from the hot aisle. To verify the effectiveness of the cold aisle containment system, a test bed which is similar to an actually existing server room was set up in the Internet Data Center(IDC) building. Comparative experiments, conventional open type cooling system and cold aisle containment system were carried out under actual conditions. The result revealed that the range of inlet temperature of the server system was $20{sim}25^{circ}C$ in an existing cooling system and the range of inlet temperature dropped below $20^{circ}C$ by the cold aisle containment system. After all, cold aisle containment system was proved to be the solution for energy saving cooling system.